COUNTY OF LOS ANGELES Hillside Structures DEPARTMENT OF
Download COUNTY OF LOS ANGELES Hillside Structures DEPARTMENT OF
Preview text
COUNTY OF LOS ANGELES
DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION
Hillside Structures
PLAN REVIEW LIST
GENERAL PROJECT INFORMATION
PLAN CHECK NO. JOB ADDRESS
DISTRICT NO
CITY
ZIP
NOTE: Numbers in the parenthesis ( ) refer to sections of the 2008 edition of the Los Angeles County Building Code, Table (T).
INSTRUCTIONS
• Corrections with circled item numbers apply to this plan check.
• In the left-hand margin of the circled corrections, please indicate the sheet number and detail or note number on the plans where the corrections are made. Resubmit marked original plans and two corrected sets of plans, calculations and this plan review list.
• Incomplete, unclear, or faded drawings or calculations will not be accepted.
• Incorporate all comments as marked on checked set of plans and calculations and these correction sheets.
GENERAL REQUIREMENTS
GENERAL
1. This ( ) new building or ( ) addition to an existing building shall be designed to comply with the provisions of Section 1613.7, Seismic Design Provisions for Hillside Buildings, as it is constructed on or into slopes steeper than 1 unit vertical in 3 units horizontal (33.3% slope). Furthermore, it also applies to the entire building even if only a portion of the building is supported on or into the slope. (1613.7.1)
2. Both the addition to the existing building, and the existing building shall comply with the provisions of Section 1613.7.
3. Identify the Base Level Diaphragm on structural
framing plans. (Base Level Diaphragm is defined as
the floor at, or closest to, the top of the highest level of
the foundation including the highest floor level
connected to the stems of the retaining/basement
walls).
(1613.7.3)
4. The base shear, including forces from the base level diaphragm, shall be resisted by direct connections from a diaphragm strut or collector provided in the base level framing to the foundation. Where the floor below the base extends to the uphill foundation, the connection shall be made directly to the foundation. (1613.7.5.1)
5. Maximum spacing between primary anchors/collectors
is 30 ft.
(1613.7.5.2)
6. Where an interior vertical lateral resisting element (e.g. interior shear walls) occurs above and in contact with the base level diaphragm, a diaphragm strut and primary anchor directly below the element shall be provided and connected to the uphill foundation. (1613.7.5.2)
7. Provide details for primary and secondary anchors and
diaphragm strut design.
(1613.7.8)
a. Wood diaphragm strut collector and wood members connected to the primary anchor shall be min. 3 x members.
b. Provide minimum 3/16-in. x 2-in. square washer and 1/4-in. x 2.5-in. square washer at 1/2-in. and 5/8-in. diameter bolts, respectively, when they are used to connect anchors to wood members.
c. The diaphragm to foundation anchorage shall NOT be accomplished by the use of toe-nailing, nails subject to withdrawal, or wood in cross-grain bending or cross-grain tension.
8. Grade beams shall extend at least 12-in. below the lowest adjacent grade and provide a minimum 24-in. distance horizontally from the bottom outside face of the grade beam to the face of the descending slope. (1613.7.10.1)
9. Where a footing or grade beam extends across a
descending slope, the stem wall, grade beam, or
footing shall extend up to a minimum 18-in. above the
highest adjacent grade. (EXCEPTION: At paved
garage and doorway entrances to the building, the
stem wall need only extend to the finished concrete
slab, provided the wood framing is protected with a
moisture proof barrier.)
(1613.7.10.2)
10. No ledgers are permitted when supporting a vertical
load of more than 100 pounds per lineal foot and
located within 48-in. of adjacent grade. Galvanized
steel ledgers and anchor bolts, with or without wood
nailers, or treated or decay resistant sill plates
supported on a concrete or masonry seat may be
used.
(1613.7.10.2)
11. All wood framed walls, including nonbearing walls,
when resting on a footing, foundation, or grade beam
stem wall, shall be supported on wood sill plates
bearing on a level surface.
(1613.7.10.3)
Hillside Structures Plan Review.doc
02-27-2008
Page 1 of 3
12. The base of isolated wood posts (not framed into a
stud wall) supporting a vertical load of 4,000-lb. or
more and the base plate for a steel column shall
comply with the following:
(1613.7.10.4)
a. When the post or column is supported on a pedestal extending above the top of a footing or grade beam, the pedestal shall be designed and reinforced as required for concrete or masonry columns. The pedestal shall be reinforced with a minimum of four No. 4 bars extending to the bottom of the footing or grade beam.
b. The base plate anchor bolts or the embedded portion of the post base, and the vertical reinforcing bars for the pedestal, shall be confined with two No. 4 or three No. 3 ties within the top 5-in. of the concrete or masonry pedestal.
c. The base plate anchor bolts shall be embedded a minimum of 20 bolt diameters into the concrete or masonry pedestal. The base plate anchor bolts and bases shall be galvanized and each anchor bolt shall have at least two galvanized nuts above the base plate.
13. All steel beams to column supports shall be positively braced in each direction. Steel beams shall have stiffener plates installed on each side of the beam web at the column. The stiffener plates shall be welded to each beam flange and the bean web. Each braced connection or structural member shall consist of at least two 5/8-in. diameter machine bolds. (1613.7.10.5)
14. Top and bottom of footings and grade beams shall be
level, or stepped when the ground slope exceeds one
vertical in ten horizontal.
(1805.1)
CALCULATIONS
Downhill Directions
15. In developing the base shear for seismic design, the response modification coefficient (R) shall not exceed 4.5 for bearing wall and building frame system. (1613.7.4.2.2)
16. Each diaphragm below the base level diaphragm shall
be designed for all tributary loads at that level using a
minimum seismic force factor not less than the base
shear coefficient.
(1613.7.7.2)
17. Provide calculations for primary anchors (at and below the base level) per Sec. 1613.7.5.
a. Primary anchor and diaphragm strut shall be provided at each foundation extending downhill, underneath interior lateral force resisting elements above and in contact with the base level diaphragm.
b. The load path and diaphragm struts shall be fully developed into the diaphragm and into the foundation. The foundation must be shown to be adequate to resist the concentrated loads from the primary anchors.
18. Provide secondary anchors in the uphill foundation
connecting to diaphragm struts in the base level
diaphragm.
(1613.7.8)
19. Maximum spacing of secondary anchors at the Base Level Diaphragms shall be uniformly distributed along the uphill diaphragm edge, spaced at maximum 4-ft. on center, and designed for a minimum force equal to the base shear coefficient times the accumulated dead load of the building tributary to that level and not less than 600 pounds per lineal foot. (The foundation need not be designed to resist these additional forces.) (1613.7.6.2)
20. Below base level, provide secondary anchors at each floor diaphragms to the uphill foundation. Such anchors shall be uniformly distributed along the uphill diaphragm edge, spaced at maximum 4-ft. on center, and designed for a minimum force equal to the base shear coefficient times the accumulated dead load of the building tributary to that level and not less than 300 pounds per lineal foot. (The foundation need not be designed to resist these additional forces.) (1613.7.7.4)
21. Primary and secondary anchors and diaphragm struts
shall be designed as follows:
(1613.7.8)
a. Design for 125% of the tributary force.
b. The 1/3 allowable stress increase permitted under Sec. 1605.3.2 shall not be used when working (allowable) stress design method is used.
c. Use seismic load factor 1.7 for steel and concrete anchorage when the strength design method is used.
d. Wood ledgers shall not be used to resist crossgrain bending or cross-grain tension.
e. Primary Anchors, splices, and connections shall be designed in accordance with provisions of section 1613.7.8.
22. Wood structural panel wall sheathing, cement plaster
and lath, gypsum wallboard, and tension-only braced
frames shall not be used to resist lateral forces below
base. Level.
(1613.7.5.4)
23. Braced frames may be used to transfer forces from the
primary anchors and diaphragm struts to the
foundation provided the lateral forces do not induce
flexural stresses in any member of the frame or in the
diaphragm struts. Deflections of frames shall account
for the variation in slope of diagonal members when
the frame is not a rectangular shape.
(1613.7.5.4)
Normal to the Downhill Direction
24. Story drift below the base level diaphragm normal to
the downhill direction shall not exceed .005 times the
story height. The total drift from the base level
diaphragm to the top of the foundation shall not
exceed 3/4-in. (Where the story height varies because
of a stepped footing or story offset, the story height
shall be an average height). The calculated story drift
shall not be reduced by the effect of horizontal
diaphragm stiffness.
(1613.7.9.4)
25. For wind level forces design, the story drift limit is .0025 or one-half of the story drift limit due to seismic design.
26. In developing base shear; the response modification
coefficient (R) used shall not exceed 4.5 for bearing
wall and building frame systems.
(1613.7.9.2)
Hillside Structures Plan Review.doc
02-27-2008
Page 2 of 3
27. The design lateral force shall be distributed to each resisting elements of varying heights in accordance with the stiffness of each individual element. (1613.7.9.5.1)
28. The stiffness of a stepped plywood shear wall may be
determined by dividing the wall into adjacent
rectangular elements, subject to the same top of wall
deflection. Sheathing and fastening requirements for
the stiffest portion shall be used for the entire wall.
Each section shall be anchored for shear and uplift at
each step. The minimum horizontal length of a step
shall be 8-ft. and the maximum vertical height of a step
shall be 2-ft. 8-in.
(1613.7.9.5.2)
29. Cement plaster and lath, gypsum wallboard, and tension-only braced frames shall not be used to resist lateral forces below the base level diaphragm. (1613.7.9.6)
ADDITIONAL COMMENTS
NOTES ON PLANS
The following notes must be included on the plans.
1. Nuts of the primary and secondary anchors fasteners shall be wrench tightened prior to inspection and covering.
2. Power-driven fasteners shall not be used to anchor sill plates except at interior nonbearing walls not designed as shear walls.
3. Exterior anchor bolts and post bases shall be galvanized and each anchor bolts shall have at least two galvanized nuts above the base plate.
4. The top of exterior pedestals must be sloped for positive drainage.
5. All main footing and grade beam reinforcement steel shall be bent into the intersecting footing and fully developed around each comer and intersection.
6. Periodic inspection by a Los Angeles County licensed deputy inspector is required for all structural connections, footings, grade beams, and retaining walls during installation.
7. Structural Observation by the Engineer or Architect of Record is required in accordance with section 1709.
Hillside Structures Plan Review.doc
02-27-2008
Page 3 of 3
DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION
Hillside Structures
PLAN REVIEW LIST
GENERAL PROJECT INFORMATION
PLAN CHECK NO. JOB ADDRESS
DISTRICT NO
CITY
ZIP
NOTE: Numbers in the parenthesis ( ) refer to sections of the 2008 edition of the Los Angeles County Building Code, Table (T).
INSTRUCTIONS
• Corrections with circled item numbers apply to this plan check.
• In the left-hand margin of the circled corrections, please indicate the sheet number and detail or note number on the plans where the corrections are made. Resubmit marked original plans and two corrected sets of plans, calculations and this plan review list.
• Incomplete, unclear, or faded drawings or calculations will not be accepted.
• Incorporate all comments as marked on checked set of plans and calculations and these correction sheets.
GENERAL REQUIREMENTS
GENERAL
1. This ( ) new building or ( ) addition to an existing building shall be designed to comply with the provisions of Section 1613.7, Seismic Design Provisions for Hillside Buildings, as it is constructed on or into slopes steeper than 1 unit vertical in 3 units horizontal (33.3% slope). Furthermore, it also applies to the entire building even if only a portion of the building is supported on or into the slope. (1613.7.1)
2. Both the addition to the existing building, and the existing building shall comply with the provisions of Section 1613.7.
3. Identify the Base Level Diaphragm on structural
framing plans. (Base Level Diaphragm is defined as
the floor at, or closest to, the top of the highest level of
the foundation including the highest floor level
connected to the stems of the retaining/basement
walls).
(1613.7.3)
4. The base shear, including forces from the base level diaphragm, shall be resisted by direct connections from a diaphragm strut or collector provided in the base level framing to the foundation. Where the floor below the base extends to the uphill foundation, the connection shall be made directly to the foundation. (1613.7.5.1)
5. Maximum spacing between primary anchors/collectors
is 30 ft.
(1613.7.5.2)
6. Where an interior vertical lateral resisting element (e.g. interior shear walls) occurs above and in contact with the base level diaphragm, a diaphragm strut and primary anchor directly below the element shall be provided and connected to the uphill foundation. (1613.7.5.2)
7. Provide details for primary and secondary anchors and
diaphragm strut design.
(1613.7.8)
a. Wood diaphragm strut collector and wood members connected to the primary anchor shall be min. 3 x members.
b. Provide minimum 3/16-in. x 2-in. square washer and 1/4-in. x 2.5-in. square washer at 1/2-in. and 5/8-in. diameter bolts, respectively, when they are used to connect anchors to wood members.
c. The diaphragm to foundation anchorage shall NOT be accomplished by the use of toe-nailing, nails subject to withdrawal, or wood in cross-grain bending or cross-grain tension.
8. Grade beams shall extend at least 12-in. below the lowest adjacent grade and provide a minimum 24-in. distance horizontally from the bottom outside face of the grade beam to the face of the descending slope. (1613.7.10.1)
9. Where a footing or grade beam extends across a
descending slope, the stem wall, grade beam, or
footing shall extend up to a minimum 18-in. above the
highest adjacent grade. (EXCEPTION: At paved
garage and doorway entrances to the building, the
stem wall need only extend to the finished concrete
slab, provided the wood framing is protected with a
moisture proof barrier.)
(1613.7.10.2)
10. No ledgers are permitted when supporting a vertical
load of more than 100 pounds per lineal foot and
located within 48-in. of adjacent grade. Galvanized
steel ledgers and anchor bolts, with or without wood
nailers, or treated or decay resistant sill plates
supported on a concrete or masonry seat may be
used.
(1613.7.10.2)
11. All wood framed walls, including nonbearing walls,
when resting on a footing, foundation, or grade beam
stem wall, shall be supported on wood sill plates
bearing on a level surface.
(1613.7.10.3)
Hillside Structures Plan Review.doc
02-27-2008
Page 1 of 3
12. The base of isolated wood posts (not framed into a
stud wall) supporting a vertical load of 4,000-lb. or
more and the base plate for a steel column shall
comply with the following:
(1613.7.10.4)
a. When the post or column is supported on a pedestal extending above the top of a footing or grade beam, the pedestal shall be designed and reinforced as required for concrete or masonry columns. The pedestal shall be reinforced with a minimum of four No. 4 bars extending to the bottom of the footing or grade beam.
b. The base plate anchor bolts or the embedded portion of the post base, and the vertical reinforcing bars for the pedestal, shall be confined with two No. 4 or three No. 3 ties within the top 5-in. of the concrete or masonry pedestal.
c. The base plate anchor bolts shall be embedded a minimum of 20 bolt diameters into the concrete or masonry pedestal. The base plate anchor bolts and bases shall be galvanized and each anchor bolt shall have at least two galvanized nuts above the base plate.
13. All steel beams to column supports shall be positively braced in each direction. Steel beams shall have stiffener plates installed on each side of the beam web at the column. The stiffener plates shall be welded to each beam flange and the bean web. Each braced connection or structural member shall consist of at least two 5/8-in. diameter machine bolds. (1613.7.10.5)
14. Top and bottom of footings and grade beams shall be
level, or stepped when the ground slope exceeds one
vertical in ten horizontal.
(1805.1)
CALCULATIONS
Downhill Directions
15. In developing the base shear for seismic design, the response modification coefficient (R) shall not exceed 4.5 for bearing wall and building frame system. (1613.7.4.2.2)
16. Each diaphragm below the base level diaphragm shall
be designed for all tributary loads at that level using a
minimum seismic force factor not less than the base
shear coefficient.
(1613.7.7.2)
17. Provide calculations for primary anchors (at and below the base level) per Sec. 1613.7.5.
a. Primary anchor and diaphragm strut shall be provided at each foundation extending downhill, underneath interior lateral force resisting elements above and in contact with the base level diaphragm.
b. The load path and diaphragm struts shall be fully developed into the diaphragm and into the foundation. The foundation must be shown to be adequate to resist the concentrated loads from the primary anchors.
18. Provide secondary anchors in the uphill foundation
connecting to diaphragm struts in the base level
diaphragm.
(1613.7.8)
19. Maximum spacing of secondary anchors at the Base Level Diaphragms shall be uniformly distributed along the uphill diaphragm edge, spaced at maximum 4-ft. on center, and designed for a minimum force equal to the base shear coefficient times the accumulated dead load of the building tributary to that level and not less than 600 pounds per lineal foot. (The foundation need not be designed to resist these additional forces.) (1613.7.6.2)
20. Below base level, provide secondary anchors at each floor diaphragms to the uphill foundation. Such anchors shall be uniformly distributed along the uphill diaphragm edge, spaced at maximum 4-ft. on center, and designed for a minimum force equal to the base shear coefficient times the accumulated dead load of the building tributary to that level and not less than 300 pounds per lineal foot. (The foundation need not be designed to resist these additional forces.) (1613.7.7.4)
21. Primary and secondary anchors and diaphragm struts
shall be designed as follows:
(1613.7.8)
a. Design for 125% of the tributary force.
b. The 1/3 allowable stress increase permitted under Sec. 1605.3.2 shall not be used when working (allowable) stress design method is used.
c. Use seismic load factor 1.7 for steel and concrete anchorage when the strength design method is used.
d. Wood ledgers shall not be used to resist crossgrain bending or cross-grain tension.
e. Primary Anchors, splices, and connections shall be designed in accordance with provisions of section 1613.7.8.
22. Wood structural panel wall sheathing, cement plaster
and lath, gypsum wallboard, and tension-only braced
frames shall not be used to resist lateral forces below
base. Level.
(1613.7.5.4)
23. Braced frames may be used to transfer forces from the
primary anchors and diaphragm struts to the
foundation provided the lateral forces do not induce
flexural stresses in any member of the frame or in the
diaphragm struts. Deflections of frames shall account
for the variation in slope of diagonal members when
the frame is not a rectangular shape.
(1613.7.5.4)
Normal to the Downhill Direction
24. Story drift below the base level diaphragm normal to
the downhill direction shall not exceed .005 times the
story height. The total drift from the base level
diaphragm to the top of the foundation shall not
exceed 3/4-in. (Where the story height varies because
of a stepped footing or story offset, the story height
shall be an average height). The calculated story drift
shall not be reduced by the effect of horizontal
diaphragm stiffness.
(1613.7.9.4)
25. For wind level forces design, the story drift limit is .0025 or one-half of the story drift limit due to seismic design.
26. In developing base shear; the response modification
coefficient (R) used shall not exceed 4.5 for bearing
wall and building frame systems.
(1613.7.9.2)
Hillside Structures Plan Review.doc
02-27-2008
Page 2 of 3
27. The design lateral force shall be distributed to each resisting elements of varying heights in accordance with the stiffness of each individual element. (1613.7.9.5.1)
28. The stiffness of a stepped plywood shear wall may be
determined by dividing the wall into adjacent
rectangular elements, subject to the same top of wall
deflection. Sheathing and fastening requirements for
the stiffest portion shall be used for the entire wall.
Each section shall be anchored for shear and uplift at
each step. The minimum horizontal length of a step
shall be 8-ft. and the maximum vertical height of a step
shall be 2-ft. 8-in.
(1613.7.9.5.2)
29. Cement plaster and lath, gypsum wallboard, and tension-only braced frames shall not be used to resist lateral forces below the base level diaphragm. (1613.7.9.6)
ADDITIONAL COMMENTS
NOTES ON PLANS
The following notes must be included on the plans.
1. Nuts of the primary and secondary anchors fasteners shall be wrench tightened prior to inspection and covering.
2. Power-driven fasteners shall not be used to anchor sill plates except at interior nonbearing walls not designed as shear walls.
3. Exterior anchor bolts and post bases shall be galvanized and each anchor bolts shall have at least two galvanized nuts above the base plate.
4. The top of exterior pedestals must be sloped for positive drainage.
5. All main footing and grade beam reinforcement steel shall be bent into the intersecting footing and fully developed around each comer and intersection.
6. Periodic inspection by a Los Angeles County licensed deputy inspector is required for all structural connections, footings, grade beams, and retaining walls during installation.
7. Structural Observation by the Engineer or Architect of Record is required in accordance with section 1709.
Hillside Structures Plan Review.doc
02-27-2008
Page 3 of 3
Categories
You my also like
American Earth Anchors
2.1 MB29.2K11.1KDesign of Transversely Prestressed Concrete Bridge Decks
5.4 MB19.8K7.7KUpgrading of Transmission Towers using Diaphragm Bracings
649.7 KB15.9K6.1KBourdon tube, capsule, diaphragm, spring diaphragm pressure
1.2 MB30.7K3.1KEvaluation of Bearing Capacity of Strip Foundation Subjected
2.2 MB16.2K4.1KButler County Building And Zoning Application For Non
535.1 KB6.2K1.2KStarkjan Where Structural Steel and Concrete Meet
338.1 KB26.8K6.7KDetailed Project Report on Bareli Water Supply Scheme
380.9 KB3.1K1.2KBearing Capacity Of Soil
1.2 MB10.8K3.9K